Fire hose testing nfpa 1962 pdf

Standard for the care, use, inspection, service testing, and replacement of fire hose, couplings, nozzles, and fire hose appliances contains the latest criteria for the inspection, care. Also, appliance users and the authority having jurisdiction shall establish a replacement schedule for their appliance that takes into consideration the use and age of the appliance and testing results. Attack fire hoses convey water from a fire pump to a fire. This nfpa hose testing ensures that your fire hoses, couplings, and nozzles are all ready for use in the case of an emergency. Nfpa 1962 20 standard for the care, use, inspection, service testing, and replacement of fire hose, couplings, nozzles, and fire hose appliances, 20 edition.

Annual service testing of fire hose is required by fire department operating procedures, and by nfpa 1962, and should be performed accordingly. Four outlet 3 gpm 500 psi electric fire hose tester. This procedure outlines the national fire protection associations nfpa standards 1962, standard for the care, use and service testing of fire hose including couplings and nozzles. The purpose of this standard is to provide requirements for the care, use, inspection, service testing, and replacement of fire hose, couplings, nozzles, and fire hose appliances so that the reliability of fire hose, nozzles, and fire hose appliances is increased when they are used at an incident. Updated referenced edition years in accordance with the nfpa manual of style. Standard on the care, use, inspection, service testing and replacement of fire hose, couplings, fire fighting nozzles and fire hose appliances this standard shall apply to the inspection, care, and use of fire hose, fire hose couplings, and fire fighting nozzles. Hose should be tested when purchased new according to the manufacturers recommendations and using this procedure.

Hose testing shall be completed annually and in conjunction with the guidelines set forth in nfpa 1962, standard for the care, use, and service testing of fire hose including couplings and nozzles. Nfpa 1962 2018 regulates the procedures for testing fire hose, at waterway we make sure that we are up to date on all regulations regarding these procedures. Fire helmet to provide head, eye and face protection. Attack fire hose shall be service tested to a minimum of 300 psi 20. Standard for the inspection, care, and use of fire hose, couplings, and nozzles and the service testing of fire hose, 2008 edition. Standard for the care, use, inspection, service testing, and replacement of fire hose, couplings, nozzles, and fire hose appliances. The procedure defined in this subsection shall be used when hose is service tested using a hose testing machine. Comply with the 2008 nfpa 1962 to make sure fire hose, nozzles, and fire hose appliances operate properly when they are used at the fire scene. Hose 5 years3 years nfpa 1962 hose connections annually 6. Supply line fire hoses bring large volumes of water from a hydrant or other pressurized source to a fire pump so it can be conveyed to an attack hose. Testing fire hose under pressure is a dangerous task and safety precautions should be followed. Fire hose testing contractor shall conduct physical inspections, pressure tests and provide test documentation on the citys fire hoses according to the national fire protection association standard 1962 for the care, use, and service testing of fire hose including couplings and nozzles, latest edition herein after known as nfpa standards. Nfpa 1962 and the iso recommend yearly testing of all fire hose. The small hole is intended to prevent the large surge of water volume that will otherwise flow through the test hose if a hose or coupling fails.

The 2018 edition of nfpa 1962, standard for the care, use, inspection, service testing, and replacement of fire hose, couplings, nozzles, and fire hose appliances, is now available online and can be read on the nfpa web site. Service requirements fire protection equipment requires. Nfpa 1961, 1962 fire hoses grainger industrial supply. One of the reasons for keeping good records of fire hose as required by nfpa 1962 is. Testing fire hose is dangerous enough without intentionally adding to the risk. It is also important that all the air in the hose be removed. National fire protection association, 1 batterymarch park, p. Nfpa 1963 contributes to a set of standards that provide manufacturers with consistent requirements for the whole fire hose system. Document all the hose locations of the fire hose on the apparatus and how it is laid out to be properly reloaded. The elements of this procedure are compliant as much as possible with nfpa 1962, standard for the. Nfpa 1962 standard for the care, use, inspection, service. This edition of nfpa 1962 was approved as an american national standard on january 17, 2003. The national fire protection association nfpa does indicate guidelines for testing, but not a firm guideline on useful life.

It is necessary equipment for conducting your nfpa 1962 flow test of nozzles, hose, and appliances, as well as comprehensive hose and nozzle. This guideline will be followed and accepted by all employees of safety 1st fire hose testing. Before storing a hose, take a look a the couplings. Standard for the care, use, inspection, service testing, and replacement of fire hose, couplings, nozzles, and fire hose appliances if a digital product is offered and you select pdf or digital access, you are purchasing a license to access nfpa information electronically. Care, use, and service testing of fire hose including. Standard for the care, use, inspection, service testing, and replacement of fire hose, couplings, nozzles, and fire hose appliances this standard provides requirements for fire hose, couplings, nozzles, and appliances in order to ensure a reasonable level of reliability when they are used at an incident. In addition to a new title, some other updates include. Conduct an acceptance test on each section of fire hose before it is placed in the hose inventory. Standard for the inspection, testing, and maintenance of. Nfpa 1962 20 standard for service testing of fire hose. These test pressures, without proper equipment, put testing personnel at risk. Hose nozzle annually and after each use nfpa 19626.

Not testing or not properly testing has the potential of both monetary and physical disaster to all involved. Nfpa 1962 flow test kit the elkhart brass flow test kit includes all essential components needed to accurately determine fire flows, friction losses, and pump discharge pressures. Inspect fire hose couplings for wear, rust, and other defects. Fire hoses are commonly used to convey water in order to stop a fire from spreading and douse the flames. This standard shall apply to the inspection, care, and use of. Each fire hose appliance shall be assigned to an identification number for use in recording its history throughout its service life. To answer your question, we need to look at national fire protection association nfpa standard 1962, standard for the care, use, inspection, service testing, and replacement of fire hose.

Nfpa 1962 sets out the recommendations how it should be done. This nfpa hose testing ensures that your fire hoses, couplings, and nozzles are all ready for use in the case of an emergen. The national fire protection association nfpa 1962, standard for the care, use, inspection, service testing, and. Hose manufactured prior to july 1987 shall be removed from service. Fire hose testing standard operating guidelines the purpose of this guideline is to explain the proper procedure for the testing of fire service hose. National fire protection associations nfpa standards 1962, standard for the care, use and service testing of fire hose including couplings and nozzles. We perform firehose hydrostatic testing as per nfpa 1962. The test shall comply with the provisions of nfpa 1962, standard for the care, use, and service testing of fire hose including couplings and nozzles. Fire hose recoupling our facility can recouple singledouble jacket hose, 1 booster hose, and 56 singledouble jacket large diameter hose per nfpa 1962. The purpose of this guideline is to explain the proper procedure for the testing of fire service hose. Users should develop a fire hose inspection and care program based on nfpa1962, standard for the inspection, care, and use of fire hose, couplings, and nozzles and the service testing of fire hose. This standard covers the care, use, inspection, service testing, and replacement of fire hose, fire hose couplings, fire fighting nozzles, and fire hose. Update to the 20 nfpa 1962 to be sure fire hose, nozzles, and fire hose appliances can operate properly for effective fire suppression featuring a revised scope and other changes, nfpa 1962.

General services division request for proposals rfp. Fire hose, couplings, firefighting nozzles and fire hose appliances. The static test requires the nozzle andor the appliance to be tested at 50psi increments for 30 seconds each until reaching 300 psi and then hold for 1 minute. Per the standard all hose is to be tested annually. Standard for the inspection, testing, and maintenance of waterbased fire protection systems 2017 edition reference.

Al petrillos great article on the impact of national fire protection association nfpa 1962, standard for the care, use, inspection, service testing and replacement of fire hose, couplings, nozzles and fire hose appliances, 20 ed. Nfpa 1962 compliant fire hose testing fire suppression. The purpose of this standard is to provide requirements for the inspection, care, and use of fire hose, couplings, and nozzles and the testing of fire hose so that the reliability of fire hose. Hose testing cheat sheet for reference montgomery county. National fire protection association, 1 batterymarch park, quincy, ma 021697471. Fire hose nfpa 1962 2008 edition hydrostatic test 14. The impact of nfpa 1962 on fire department hose testing. Technical bulletin hose testing information and no. Your lifeline for water supply ensure that your hose wont fail you when you need it most. If a fire pump on a fire department apparatus is used for service testing of fire hoses, the procedures in nfpa 1962 must be followed including the use of a fire department gate valve with a.

Personnel must remain behind on the intake side the hose. This document complements nfpa 1962, standard for the care, use, inspection, service testing, and replacement of fire hose, couplings, nozzles, and fire hose appliances, which is for fire hose operators. This standard contains the latest criteria for the. Copyright by national fire protection association nfpa. Standard on the care, use, inspection, service testing and replacement of. Replacement if appliance fails any, it shall be removed and repaired or replaced. Nfpa 196220 standard for the care, use, inspection. Per the standard even if hose has never been used, but is more than one year old, the hose must be tested prior to use. Using a hose testing machine if necessary, see nfpa 1962 2018 edition for additional details. That program should also address the retirement of fire hose. This pump meets or exceeds the testing standards for nfpa 1962. During a visual fire hose inspection or service testing, nfpa 1963 requires that couplings with certain defects are repaired or the hose replaced.

The four outlet 3 gpm 500 psi electric fire hose testing machine is an essential tool for testing fire hose, sprinkler systems, and pressure vessels. As the pressure rises, the shorter length will allow the hose to assume a natural elongation, creating less warp in the hose. Service requirements fire protection equipment requires care. Nfpa 1901, standard for automotive fire apparatus, 2016 edition. Nfpa 24, standard for the installation of private fire service mains and their appurtenances, 2016 edition. We then provide you with complete documentation of test records.

Hose testing all fire hose tested will be tested in accordance with. We offer very competitive rates for all of your hose testing needs. Statement of problem and substantiation for public input. The procedure fire hose should be tested as set forth in nfpa pamphlet 1962, standard for the care, use, and service testing of fire hose including couplings and nozzles, latest edition. Fire hose inspection frequency sections nfpa 1962 hose annual 24. This standard shall apply to the inspection, care, and use. Chapter 6 care, use, inspection, maintenance, service testing, and replacement of fire. Before hose is pressurized, all personnel participating in hose testing must be wearing a helmet and eye protection. Nfpa 1962 compliant fire hose testing fire suppression systems. Replacing fire hose municipal technical advisory service. We can also accomodate the testing requirements of many other types of hoses as well raw water, utility, breathing air. If necessary, see nfpa 1962 2018 edition for additional details. Oct 14, 2014 suggested test procedure automatic nozzle.

Test the gpm and psi accuracy of your handline fire nozzles per nfpa 1962 to ensure correct functionality and flag nozzles needing repair or replacement. National fire protection association nfpa 1962, standard for the care, use, inspection, service testing and replacement of fire hose, couplings, nozzles and fire hose appliances 20 ed. With hose testing properly completed, per nfpa standards, liability is reduced to the fire department, to the firefighters and to the community they protect. Nfpa 1962, 20 edition requires nozzles and fire hose appliances to be static tested annually. This bulletin serves to remind testing personnel of specific safety concerns addressed in nfpa 1962.

Reduced risk from fire hose testing most attack hoses manufactured after july 1987 require 300 or 400 psi annual service testing see nfpa 1962. From nfpa 1962, care, use and services testing of fire hose including couplings and nozzles. The 1 hp electric pump is operated off of 110220 volt 50 or 60 hertz service. Nfpa 1962 standard for the care, use, inspection, service testing, and replacement of fire hose, couplings, nozzles, and fire hose appliances. The process can be sometimes confusing, but the experts at fire protection. Standard for the inspection, care, and use of fire hose, couplings and nozzles. A record of each fire hose appliance shall be maintained from the time the appliance is purchased until it is discarded. Because there is a potential for catastrophic failure during the service testing of fire hose, it is. National fire protection association nfpa 1962, standard for the care, use, inspection, service testing and replacement of fire hose. Nfpa 1962 firehouse forums firefighting discussion.